| Customization: | Available |
|---|---|
| Breaking Capacity: | High Voltage Circuit Breakers |
| Operation: | Electric Type |
| Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
|---|
| Payment Methods: |
|
|---|---|
| Support payments in USD |
| Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
|---|
| Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
|---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency




| No | Item | Unit | Value | |
| 1 | Rated voltage | kV | 40.5 | |
| 2 | Rated insulation level | 1 min power frequencyDry test(fracture, inter-phase,to earth)Wet test(to earth, external insulation) |
kV | 95 85 |
| Lightning impulse withstand voltage(peak) | 185 | |||
| 3 | Rated current | A | 1250,1600,2000, 2500 |
|
| 4 | Rated short circuit breaking current | kA | 20,25,31.5 | |
| 5 | Rated short circuit making current(peak) | kA | 50,63,80 | |
| 6 | Rated peak withstand current | kA | 50,63,80 | |
| 7 | Rated short time withstand current | kA | 20,25,31.5 | |
| 8 | Rated operating sequence | 0-0.3S-CO-180S-CO | ||
| 9 | Rated short circuit breaking current breaking number | times | 20 | |
| 10 | Rated short circuit duration | s | 4 | |
| 11 | Breaking time | S | ≤0.09 | |
| 12 | Mechanical life | times | 10000 | |
| 13 | Newly manufactured vacuum interrupter | Ps | ≤1.33×10-3 | |
| Vacuum interrupter during 20-year storage time | <6.6×10-2 | |||
| 14 | Circuit breaker net weight | kg | 800 | |
| 15 | Clearance between open contacts | mm | 22±2 | |
| 16 | Contact travel | mm | 4±1 | |
| 17 | Average opening speed | m/s | 1.4-1.7 | |
| 18 | Average closing speed | m/s | 0.4-0.7 | |
| 19 | Contact closing bounce time | ms | ≤3 | |
| 20 | Inter-phase opening and closing synchronism | ms | ≤2 | |
| 21 | Closing time | ms | 50≤t≤200 | |
| 22 | Opening time | ms | 30≤t≤60 | |
| 23 | Each phase main circuit DC resistance (not includeCT internal resistance) |
μQ | ≤100 | |
| 24 | Dynamic and fixed contact cumulative thickness allowed to wear | mm | 3 | |
| 25 | Rated contact pressure | N | 2500±200 | |








1. Are you a trading company or manufacturer ?