Product Description
When the 12kV overhead distribution line T branch line or the end user fails, when the protection action time limit of the inlet switch and the protection time limit of the substation outlet switch cannot be reasonably adjusted, it will cause the substation outlet switch to trip. lf the fault is permanent in nature and the substation coincidence will be unsuccessful, a local disturbance within the medium-voltage user boundary will outage the entire 12kV distribution line. lf an outdoor demarcation circuit breaker is installed at the T junction or the user end (responsibility demarcation point), and the fault (overcurrent,short circuit, single-phase ground, etc.) is confirmed within the user boundary after judgment, the fault is automatically isolated, which can ensure the normal power consumption of users in non-fault areas. The application of ZW32-12F outdoor high-voltage intelligent demarcation vacuum circuit breaker (watchdog) on 12kV feed overhead line can avoid the cascade power outage of trouble-free lines, reduce the scope of faulty power outages, shorten the power outage time of users, and protect the safe operation of the main network. And with fault detection function, protection control function and communication function, it can realize automatic cutting of single-phase ground fault and automatic isolation of short-circuit fault between phases. The installation point is suitable for the dividing point of responsibility for the incomingline of the 12kV distribution line user, and can also be applied to the branch line connection that meets the requirements.



Product Parameters
Ambient temperature: not higher than +40°C , not lower than -15°C ;
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%;
The altitude does not exceed 1000 meters;
The intensity ofthe earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements, they can be put forward when ordering, and our company will give the greatest satisfaction.

Technical parameters
project |
unit |
parameter |
Rated voltage |
kV |
12 |
Rated current |
A |
630.1250 |
Rated frequency |
Hz |
50 |
Power frequency withstand
voltage(1min) |
Dry(interphase,ground/fracture) |
kV |
42/48 |
Wet test(ground and external insulation) |
34 |
Lightning impulse withstand current(peak)(phase-to-phase,ground/break) |
kA |
75/85 |
Rated short-circut breaking current |
kA |
20 |
25 |
Rated short-circuit closing current(peak) |
kA |
50 |
63 |
Rated bee value withstand current |
kA |
50 |
63 |
4S short-term withstand current |
kA |
20 |
25 |
Rated operating cycle |
|
Minutes-0.3s-combined points-180s-combined points |
Rated number of short-circuit current breaks |
times |
30 |
Mechanical life |
times |
10000 |
The secondary circuit is 1min power frequency withstand voltage |
kV |
2 |
Contact spacing |
mm |
9±1 |
Contact overtravel |
mm |
2.5±1 |
Opening speed |
m/s |
1.1±0.3 |
Closing speed |
m/s |
0.6±0.2 |
Contact closure bounce time |
ms |
≤2 |
The distance between the centers |
mm |
340±2 |
Three-phase split and close with different periodicity |
ms |
≤2 |
Conductive loop resistance of each phase |
μΩ |
≤80(with isolation≤150) |
weight |
kg |
Without isolation 110 |
With isolation 140 |
Company Profile


Certifications

company workshop

Packaging & Shipping




1. Are you a trading company or manufacturer ?
We are a professional factory with 10 years experience in the field of High and Low voltage switchgears,Substation,transformers,cable distribution box and various electrical equipment, such as vacuum circuit breaker , load break switch etc.
Our factory is the excellent supplier of State Grid Corporation of China.
2. Do you accept customized serveice ?
We offer OEM/ODM service , can print your logo on product . our professional technical and quotation team can provice a satisfied project according to your drawing and parameters.
3. What is your MOQ?
Our MOQ is 1 piece.
4. How long is your delivery lead time ?
It depends on your product requirement and quantity . Generally , 5~10 working days is available
5. How do you solve quality problems?
Please porvide detailed photoes of quality problems. our technical and quality testing department will analyse.we will make a satisfied soluton within 2 days .
6. What is your payment terms ?