Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Load Break Switch |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
FKN12-12 indoor high-voltage compressed gas load switch (hereinafter referred to as FKN12-12 load switch) is a three-phase high-voltage switchgear with a rated voltage of 12kV and a rated frequency of 50Hz, which is used to separate load current, closed-loop current, no-load transformer and current charging current, and close short-circuit current. A load switch equipped with a grounding switch can withstand short-circuit currents.
FKRN12-12 indoor high-voltage load switch fuse combination electrical appliance (hereinafter referred to as FKRN12-12 combination electrical appliance) is an indoor switchgear combined with FKN12-12 load switch and S LAJ-12 (XRNT -10) high-voltage current limiting fuse.
It can reliably cut off any current up to the short-circuit current; The load switch breaks the current, the fuse breaks the short-circuit current,and the joint interrupts any current between the working current and the full short-circuit current, while the fuse opens the load switch through its impactor.
project | unit | FKN12-12 | FKRN12-12 |
Rated voltage | kV | 12 | |
Rated frequency | Hz | 50 | |
Rated current | A | 630 | 100 |
Lightning impulse withstand voltage | kV | To ground and phase 75,isolation 85 | |
1min power frequency withstand voltage | kV | To ground and phase 42,isolation 48 | |
Rated thermally stable current | kA | 20(4S) | |
Rated dynamic stability current | kA | 50 | |
Rated closing current(peak) | kA | 50 | 50 |
Rated short-circuit breaking current(given value) | kA | 31.5 | |
Maximum 12.tMax at critical breaking current | A2S | By dissolver characteristic curve | |
Minimum breaking current | kA | Press the fuse characteristic curve | |
Rated transfer current | kA | 1.5 | |
Maximum breaking current(reference) | kA | 1.8 | |
Open no-load transformer capacity | kVA | 1250 | |
Rated cable charging current | A | 10 | |
Rated number of active load current cuts | times | >100 | |
The impactor touches the load switch opening time | S | >0.06 | |
The grounding switch thermally stabilizes the current | kA | 20(2S) | |
Grounding switch thermally stable current(peak) | kA | 50 | |
The motor operates the supply voltage | V | AC DC 110,220 |